Users Guidehttp://www.dasieee.come-mail: [email protected] SeriesRadio Telemetry Systems
Installation/OperationN O T E S...
7. CONTROL BOARD SCHEMATIC7.1 The following is the DATAFLOW RTU Control Board schematic.Figure A1 - Control Board Schematic( A-5 )
( A-6 )RITRON, INC.Installation/ Operation8.3 SCHEMATIC REFERENCE NUMBER PARTS LIST, RTU-CNTL, 03/05/98REF. PART NO. DESCRIPTION Y XCAPACIT
DATAFLOW RTURITRON, INC.( A-7 )REF. PART NO. DESCRIPTION Y XC 123 152C6226 22uf 10V 6.0 X 3.2 CHIP TANTALUM CAP 0.028 2.955C 124 152AB334 .33MF
( A-8 )RITRON, INC.Installation/ OperationR 106 47100102 1K OHM 0805 CHIP RES 1.337 3.914R 107 47100106 RESISTOR, 10M OHM 0805 5% CHIP 2.473 4.155R 10
DATAFLOW RTU9. RF BOARD SCHEMATIC9.1 Contact Omega for more detailed information on the DTX RF board schematic.10.RF BOARD LAYOUT10.1 Contact Omega f
Installation/OperationCONNECTOR PIN NAME DESCRIPTIONUser Input/ Output: 1 R11 Relay 1 Contact 1 2 R12 Relay 1 Contact 2 3 R21 Relay 2 Contact 1 4 R2
DATAFLOW RTU11.1.4 CONNECTIONSCONNECTOR PIN NAME DESCRIPTIONExt. Power/ Serial: 1 A Serial Pair AJ105 (X3.8 Y0.2) 2 B Serial Pair B 3
Installation/Operation12.1.5 PJ105 (Y 2.7 - X 1.2): This jumper setting determines if configurable I/O 2 is set for voltage or currentloop analog out
DATAFLOW RTU14.1.2 Optional mounting bracket OMEGA part number RTU-25104600 is available for DATAFLOW RTU. Toinstall this bracket to the case, remove
Servicing North America:USA: One Omega Drive, Box 4047ISO 9001 Certified Stamford, CT 06907-0047Tel: (203) 359-1660 FAX: (203) 359-7700e-mail: info@om
Installation/Operation( A-14 )15. POWER15.1 The DATAFLOW RTU small enclosure (S) may be purchased with the delete internal power (D) option.The RTU po
DATAFLOW RTU( A-15 )15.5.3 The following calculations apply to RTU-BATNICD, using a 14V source.R1 = (14 - 0.4 - 12) / .05 = 32 WPR1 = (14 - 0.4
Installation/Operation( A-16 )19. DIGITAL OUTPUTS19.1 The two digital outputs are defined to be pins 1-3 and 2-4. These outputs are two dry-contact cl
DATAFLOW RTU( A-17 )DATAFLOW RTUPOWER OUTANALOG INANALOG IN GND250 ΩRESISTORSENSOR250 ΩRESISTORDATAFLOW RTUPOWER OUTANALOG INANALOG IN GNDSENSORVEXCI
Installation/Operation( A-18 )21.1.2 If the output pin is to be a current sink, correctly set the hardware configuration. The pin is to behardware con
Software/Programming DATAFLOW RTUSoftware/ Programming Table of ContentsSECTION TITLE PAGE NO.1 Introduction B-12 Operation B-13 Microprocessor U
DATAFLOW RTU1. INTRODUCTION1.1 The DATAFLOW RTU from OMEGA is a complete wireless telemetry system designed todeliver industrial instrumentation sign
Software/Programming4.2.1 The AC Power Supply, OMEGA part number RTU-PS, converts 110 Volts AC to a DC voltagefor use by the DATAFLOW RTU. The power s
DATAFLOW RTU4.2.4 RTU Programming Software Disk, OMEGA part number RTU-PCPS-3.0, provided with theprogramming kit to facilitate configuration of a DA
Software/Programming5.5 The <F5>, <F6> and <F9> function keys are used in several fields of the programmingsoftware to perform file
WARRANTY/DISCLAIMEROMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanshipfor a period of 13 months from dat
DATAFLOW RTU>>> RTU PROGRAMMER VERSION 3.03 960724 HELP FILE <<<1.0 RTU System Configuration Screen:The system configuration screen
Software/Programming>>> RTU PROGRAMMER VERSION 3.03 HELP FILE <<<(continued)Enabling RF spy mode on one RTU allows that RTU to repor
DATAFLOW RTU>>> RTU PROGRAMMER VERSION 3.03 HELP FILE <<<(continued)1.5 Message LineThe third line from the bottom of the RTU s
Software/Programming>>> RTU PROGRAMMER VERSION 3.03 HELP FILE <<<(continued)If this input is selected as a Digital input, the value
DATAFLOW RTU>>> RTU PROGRAMMER VERSION 3.03 HELP FILE <<<(continued)Input # 1 # 2 # 3 # 4 # 5 # 6 BATTERYTag NameInitiate Xmi
Software/ProgrammingThe SCADA controller is directly connected to RTU 1 by a serial link. The SCADA controllerpolls RTU 1, RTU 2, RTU 3, and MODBUS De
DATAFLOW RTU6. MODBUS MEMORY MAP6.1 The DATAFLOW RTU supports three types of MODBUS messages; it will recognize:· READ OUTPUT REGISTER function code
Software/Programming6.3.2 DECIMAL MODBUS MEMORY MAP AND TABLES6.3.2.1 Decimal MODBUS memory map for stored data access:Message RTU ID InputVoltage In
DATAFLOW RTU6.4 Load the FULL SCADA CONFIG, using RTU Programming Software. The configuration isstored in RTU RAM, which has a large capacitor to hol
Software/Programming7.2 COPYING CONFIGURATION between DATAFLOW RTU Units: This note explains how to preserveprogrammed default settings.TO COPY CONFIG
Installation/Operation/Software/Programming Manual DATAFLOW RTUOWNER INFORMATIONFCC REGULATIONSLICENSINGThe FCC requires you to obtain a station lice
DATAFLOW RTUEXAMPLE 18.2 EXAMPLE 1 is a pair of DATAFLOW RTUs having two digital channels and two analogchannels in each direction; each RTU is conf
Software/ProgrammingEXAMPLE 1 (continued)8.2.3.3 The FAIL-SAFE STATE table controls RTU outputs when the RTU detects a loss of RFlink. Because Exampl
DATAFLOW RTUEXAMPLE 28.3 EXAMPLE 2 configures three DATAFLOW RTUs with one connected to two others. RTUID 1 has two digital inputs, two digital outp
Software/ProgrammingEXAMPLE 2 (continued)8.3.4.2 The FAIL-SAFE STATE table controls the RTU outputs when the RTU detects a loss ofRF link. Because Ex
DATAFLOW RTUEXAMPLE 38.4 EXAMPLE 3 configures DATAFLOW RTU inputs to illustrate THRESHOLD, DEAD ZONEand TIME DELAY. The configuration includes Digita
Software/ProgrammingEXAMPLE 48.5 EXAMPLE 4 configures two RTUs to illustrate XMIT CHECK-IN and RCV CHECK-IN intervals, and R (Revert) FAIL-SAFE STATE
DATAFLOW RTUEXAMPLE 58.6 EXAMPLE 5 illustrates a DATAFLOW RTU system with one RTU configured as a repeater.Connect the RTUs according to the followi
Software/ProgrammingEXAMPLE 68.7 EXAMPLE 6 demonstrates the DATAFLOW RTU as a MODBUS device using direct dataaccess. The configuration consists of a r
DATAFLOW RTUEXAMPLE 6 (continued)8.7.5 Execute the SYSTEM MONITOR - UTILITIES screen to view two ID fields:The top left field on the UTILITIES scree
Software/ProgrammingEXAMPLE 78.8 EXAMPLE 7 demonstrates the DATAFLOW RTU as a MODBUS device using stored dataaccess. The configuration consists of a r
Installation/Operation/Software/Programming Manual DATAFLOW RTUCAUTIONS1. ALL DIGITAL INPUTS, ANALOG INPUTS, ANALOG OUTPUTS, ANDMEASUREMENTS OF THE D
DATAFLOW RTUEXAMPLE 88.9 EXAMPLE 8 illustrates the DATAFLOW RTU performing a MODBUS modem function.Configuration files EXP8ID1 and EXP8ID2 allow two
( B-26 )RITRON, INC.Software/ ProgrammingFigure B1 - EXAMPLE 1 RTU ID 1 Wiring Diagram
DATAFLOW RTURITRON, INC.( B-27 )Figure B2 - EXAMPLE 1 RTU ID 2 Wiring Diagram
( B-28 )RITRON, INC.Software/ ProgrammingFigure B3 - EXAMPLE 2 RTU ID 1 Wiring Diagram
DATAFLOW RTURITRON, INC.( B-29 )Figure B4 - EXAMPLE 2 RTU ID 2 Wiring Diagram
( B-30 )RITRON, INC.Software/ ProgrammingFigure B5 - EXAMPLE 2 RTU ID 3 Wiring Diagram
DATAFLOW RTURITRON, INC.( B-31 )Figure B6 - EXAMPLE 4 RTU ID 1 Wiring Diagram
( B-32 )RITRON, INC.Software/ ProgrammingFigure B7 - EXAMPLE 4 RTU ID 2 Wiring Diagram
DATAFLOW RTURITRON, INC.( B-33 )Figure B8 - EXAMPLE 5 RTU ID 1 Wiring Diagram
( B-34 )RITRON, INC.Software/ ProgrammingFigure B9 - EXAMPLE 5 RTU ID 2 Wiring Diagram
Installation/Operation DATAFLOW RTUInstallation/ Operation Table of ContentsSECTION TITLE PAGE NO. 1 Introduction A-1 2 Ope
DATAFLOW RTURITRON, INC.( B-35 )Figure B10 - EXAMPLE 5 RTU ID 3 Wiring Diagram
( B-36 )RITRON, INC.Software/ ProgrammingFigure B11 - EXAMPLE 6 RTU ID 1 Wiring Diagram
DATAFLOW RTURITRON, INC.( B-37 )Figure B12 - EXAMPLE 6 RTU ID 2 Wiring Diagram
Where Do I Find Everything I Need forProcess Measurement and Control?OMEGAOf Course!TEMPERATURE Thermocouple, RTD & Thermistor Probes, Connectors
DATAFLOW RTU1. INTRODUCTION1.1 The DATAFLOW RTU from OMEGA is a complete wireless telemetry system designed todeliver industrial instrumentation sign
Installation/Operation4. PART NUMBER DEFINITION4.1 The following is a list of the part numbers available at the printing of this material.RTU-X X X -
DATAFLOW RTU( A-3 )6 SPECIFICATIONS6.1 SYSTEM SPECIFICATIONSFCC ID:........... RTU-150 - AIERIT04-150; RTU-450 - AIERIT